Air Flow Transducers

Back to Sensors Guide

Logic Beach offers a line of air flow sensors for use with dry air and nitrogen.  These transducers are commonly employed in compressed air systems for long term monitoring as well as during audits to more accurately understand the compressed air supply requirements and loading.

The flowmeters clamp onto a pipe, with two flow sensing probes projecting into the pipe through 3/16-in. drilled holes (clamp on drill guides are available for installation).  The flowmeter seals directly to the pipe; no cutting or welding is required for installation. Because each flowmeter is made and calibrated for a specific size of pipe, the integral digital display indicates  flow directly, with no setup or adjustment required.

The meter measures flow by maintaining one probe warmer than the other.  It calculates the gas mass velocity from the amount of heat required, and then calculates the flow on the basis of pipe cross-sectional area. The flow rate, in scfm, is shown on a large, four-digit display.  The flowmeters come with 4-20mA and pulse outputs standard as well as an optional Modbus RTU slave option permitting remote display, data collection and flow profiling with compatible data logging and reporting instruments from Logic Beach. 

Two models (5200 and 5400) are available for two different ranges of pipe dimensions,  The 5200 is compatible with ½” to 2” pipe and the 5400 is compatible with 2” to 6” pipe.

Drill guides are required for installation and are available from Logic Beach for the various models. 

5200 Model Common Specifications:  

Accuracy: 5 percent of reading plus one percent of full scale at air temperatures between 40 and 120 degrees F
Fluids: Compressed air and nitrogen
Operating pressure: 30 to 170 psig for best accuracy 200 psig maximum on Sch. 40 steel and Type L copper; consult CDI for other materials.
Input power: 250 mA at 18 to 24 Vdc (unit is supplied with 120Vac/18Vdc wall adapter.
Pulse Output (standard): 5 pulses per standard cubic foot of air (SCFM) in all meter models models. Output is an Open Collector transistor which shorts to the flowmeter negative supply. Current limiting is required to protect internal switch.
4-20mA Output (standard): Isolated analog 4-20mA current output requires external Vdc loop power for operation. Can be powered from the same supply powering the flow meter or a separate Vdc supply. Minimum of 9Vdc is required (burden) across the 4-20mA terminals for operation.
Modbus Output (optional): Modbus RTU Slave via RS-485 (2-wire) allowing for multiple meters to be networked to a single IntelliLogger data logging and reporting instrument.  Factory option, specify at time of order.


Wetted materials: Stainless steel, gold, thermal epoxy and Viton (seal)
Clamping Ring material: Aluminum
Display: Four-digit LED display
Response time: One second to 63 percent of final value
Price Range: ~$350 to $500

5200 Series Models by Pipe Size:

AVAILABLE SIZES
Nom Size
Rangea
(scfm)
Model No. for
Sch 40 Steel
Model No. for
Type L Copper
1/2 in.
0.4 - 30
5200-05S
..
3/4 in.
0.6 - 40
5200-07S
5200-07C
1 in.
1 - 80
5200-10S
5200-10C
1 - 1/4 in.
1 - 150
5200-12S
5200-12C
1-1/2 in.
2 - 200
5200-15S
5200-15C
2 in.b
3 - 350
5200-20S
5200-20C
25 mm
1 - 60
25M for 22mm x 25 mm Aluminum
40 mm
2 - 200
40M for 36mm x 40 mm Aluminum

(a) Accuracy will be reduced when flow is outside of specified range. Milliamp scale ranges differ, see label inside meter.

 

5400 Model Common Specifications:

Accuracy, calibrated range: 5 percent of reading plus one percent of full scale at air temperatures between 40 and 120 degrees F
Accuracy, extended range: 7 percent of reading from rated full scale to 150
percent of calibrated range, at air temperatures between 40 and 120 degrees F
Fluids: Compressed air and nitrogen
Operating pressure: 200 psig maximum on Sch. 40 steel and Type L
Copper; consult Logic Beach about other materials.
Input power: 250 mA at 18 to 24 Vdc
Pulse Output (standard): 5 pulses per standard cubic foot of air (SCFM) in all meter models models. Output is an Open Collector transistor which shorts to the flowmeter negative supply. Current limiting is required to protect internal switch.
4-20mA Output (standard): Isolated analog 4-20mA current output requires external Vdc loop power for operation. Can be powered from the same supply powering the flow meter or a separate Vdc supply. Minimum of 9Vdc is required (burden) across the 4-20mA terminals for operation.
Modbus Output (optional): Modbus RTU Slave via RS-485 (2-wire) allowing for multiple meters to be networked to
a single IntelliLogger data logging and reporting instrument. Factory option, specify at time of order.
Wetted materials: Stainless steel, gold, epoxy and Viton (seal)
Ring material: Aluminum
Display: Four-digit LED display
Response time: One second to 63 percent of final value
Price Range: ~$500 to $1700

5400 Series Models by Pipe Size:

AVAILABLE SIZES
Nom Sizea
Calibrated
Rangeb(scfm)
mA full scale (scfm)
Model No. for
Sch 40 Steel
Model No. for
Type L Copper
2 in.
3 - 350
600
5400-20S
5400-20C
2.5 in.
5 - 500
800
5400-25S
5400-25C
3 in.
7 - 700
1000
5400-30S
5400-30C
4 in.
15 - 1200
2000
5400-40S
5400-40C
5 in.
20 - 1500
2400
5400-50S
..
6 in.b
30 - 2000
3000
5400-60S
..
63mm
5 - 500
800
63M for 63mm x 59 mm Al

(a) For metering smaller pipe sizes, lease see our Series 5200 flowmeters.
(b) Accuracy will be reduced when flow is outside of the specified range.